The simple method
- List everything that will run at the same time.
- Add up the running power in kW.
- Divide by 0.8, the usual power factor, to get kVA.
- Add 20 to 25 percent headroom for motor starts and growth.
Typical loads
| Equipment | Running power |
|---|---|
| 1.5 ton split AC | about 1.8 kW |
| 5 ton spot cooler | about 6 kW |
| Package AC, 10 ton | about 12 kW |
| Industrial air cooler | about 0.5 kW |
| LED screen, per sqm | about 0.3 to 0.5 kW |
| PA system, medium event | about 3 to 5 kW |
| Catering: fryer, oven, warmers | about 10 to 25 kW |
| LED lighting for a 200 sqm tent | about 2 to 4 kW |
Worked examples
| Job | Load | Suggested generator |
|---|---|---|
| Garden event, 100 guests, lights, sound, 4 coolers | about 10 kW | 20 to 30 kVA |
| Villa with 8 split ACs and kitchen | about 25 to 35 kW | 45 to 60 kVA |
| 200 guest tented wedding with AC and catering | about 70 to 100 kW | 100 to 150 kVA |
| Site with cabins and tools | about 20 to 40 kW | 30 to 60 kVA |
| Tower crane | about 100 to 150 kW | 200 to 250 kVA |
Mistakes to avoid
- Forgetting motor start loads: AC compressors and pumps draw 3 to 6 times their running power for a second.
- Running a generator below 30 percent load for days, which causes wet stacking. Size it right, not huge.
- Ignoring three phase: large AC and catering equipment often need a three phase supply.